🇺🇸 Journeyman/Master Electrician License Exam · subject
Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment Syllabus
The Wiring Methods, Materials, and Equipment syllabus for Journeyman/Master Electrician License Exam in full: 3 chapters, 10 topics and 23 sub-topics, every one listed below, plus 51 Wiring Methods, Materials, and Equipment flashcards with answers.
Wiring Methods, Materials, and Equipment syllabus: all 3 chapters
Expand any chapter to see its topics and sub-topics.
-
Conductors and Insulation
3 topics- Conductor Types and Temperature Ratings
- THHN, THWN-2, XHHW-2 and 60/75/90 C columns
- Termination temperature limitations (110.14(C))
- Ampacity and Adjustment Factors (Article 310)
- Table 310.16 ampacities
- Ambient temperature correction factors
- Conductor bundling/fill adjustment for 4 or more current-carrying conductors
- Conductor Identification and Color Coding
- Grounded conductor (white/gray) requirements
- High-leg (delta) identification
- Conductor Types and Temperature Ratings
-
Raceways, Boxes, and Fittings
4 topics- Conduit and Tubing Types
- RMC, IMC, EMT, PVC, FMC, and LFMC applications
- Support spacing and securing requirements
- Conduit Fill and Bending
- Chapter 9 Tables 1, 4, and 5 fill calculations
- Maximum 360 degrees of bend between pull points
- Minimum bending radius
- Outlet, Device, and Junction Box Fill
- Box fill calculation (314.16)
- Conductor, device, clamp, and equipment grounding allowances
- Pull and junction box sizing (314.28)
- Cable Wiring Methods
- NM, AC, MC, and UF cable applications and limitations
- Securing and support intervals
- Conduit and Tubing Types
-
Switches, Receptacles, and Luminaires
3 topics- Switches (Article 404)
- Three-way and four-way switching
- Grounding of snap switches
- Receptacles and Cord Connectors (Article 406)
- Tamper-resistant and weather-resistant requirements
- Receptacle mounting and faceplate rules
- Luminaires and Lighting (Article 410)
- Clearances in clothes closets
- Luminaires in wet and damp locations
- Switches (Article 404)
Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment flashcards — 51 questions with answers
In NEC conductor insulation type letters, what do the letters T, H, HH, W, and N each indicate?
T = thermoplastic insulation; H = heat-resistant ($75^{\circ}\text{C}$); HH = high heat-resistant ($90^{\circ}\text{C}$); W = moisture-resistant (suitable for wet locations); N = nylon outer jacket.
What are the temperature ratings of THHN and THWN-2 conductor insulation, and where may each be used?
THHN is rated $90^{\circ}\text{C}$ in dry/damp locations only. THWN-2 is rated $90^{\circ}\text{C}$ in dry, damp, and wet locations. Most building wire is dual-rated THHN/THWN-2.
For most general building wiring, what is the highest conductor temperature rating that may actually be used for ampacity, and why?
Even with $90^{\circ}\text{C}$ insulation, terminations on equipment limit ampacity to the $60^{\circ}\text{C}$ column for circuits $\leq 100\,\text{A}$ (or #14-#1 AWG) and the $75^{\circ}\text{C}$ column above that, per NEC 110.14(C). The $90^{\circ}\text{C}$ column is generally used only for derating calculations.
Which conductor types are listed for direct burial, and which common insulation is rated for use in wet locations?
USE and UF cable are listed for direct burial. For wet locations, conductors marked W (such as THWN-2, XHHW-2) are required; THHN alone is not permitted in wet locations.
What is the difference between an aluminum conductor terminal marked CO/ALR versus one marked AL-CU?
CO/ALR identifies switches and receptacles ($15$ and $20\,\text{A}$) listed for direct connection to aluminum wire. AL-CU marks lugs/connectors rated for both aluminum and copper conductors. Devices marked only CU are copper-only.
Define ampacity as used in NEC Article 100/310.
Ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
What is the ampacity of a single THWN-2 copper conductor at the $75^{\circ}\text{C}$ column for sizes 12, 10, and 8 AWG (Table 310.16)?
12 AWG $= 25\,\text{A}$, 10 AWG $= 35\,\text{A}$, 8 AWG $= 50\,\text{A}$. (Note the small-conductor overcurrent limits of 310.16 still cap 14/12/10 AWG at 15/20/30 A.)
State the conductor ampacity adjustment factors of NEC Table 310.15(C)(1) for 4-6, 7-9, and 10-20 current-carrying conductors in a raceway.
4-6 conductors: $80\%$; 7-9 conductors: $70\%$; 10-20 conductors: $50\%$ of the base ampacity.
Write the formula for the temperature-corrected, derated ampacity of a conductor.
$$I_{\text{allowed}} = I_{\text{table}} \times F_{\text{temp}} \times F_{\text{adj}}$$ where $F_{\text{temp}}$ is the ambient temperature correction factor (Table 310.15(B)) and $F_{\text{adj}}$ is the conductor count adjustment factor (Table 310.15(C)(1)).
Worked example: Eight 8 AWG THHN copper conductors ($90^{\circ}\text{C}$ base $= 55\,\text{A}$) share a raceway in a $40^{\circ}\text{C}$ ambient. What is the adjusted ampacity?
Temp correction at $40^{\circ}\text{C}$ for $90^{\circ}\text{C}$ wire $= 0.91$; adjustment for 7-9 conductors $= 0.70$. $$55 \times 0.91 \times 0.70 \approx 35\,\text{A}$$
Which conductors count as 'current-carrying' for adjustment factors, specifically regarding neutrals and grounds?
The equipment grounding conductor is never counted. A neutral carrying only the unbalanced current of a balanced system is not counted, but a neutral on a 3-wire circuit from a 4-wire wye (carrying harmonic/major load) IS counted as current-carrying.
What is the standard color coding for grounded (neutral) conductors and equipment grounding conductors per NEC 200.6 and 250.119?
Grounded/neutral conductors: white or gray, or three continuous white stripes. Equipment grounding conductors: green, green with yellow stripe, or bare.
In a 208Y/120 V three-phase system, what is the common phase color code for A, B, and C?
Phase A = black, Phase B = red, Phase C = blue. (The neutral is white/gray.) Colors above 50 V are not mandated by NEC for ungrounded conductors but this is the widely used convention.
What color identification is conventionally used for a 480Y/277 V three-phase system's phases?
Phase A = brown, Phase B = orange (or purple), Phase C = yellow, with gray neutral. This distinguishes 480 V from 208 V (black/red/blue) systems.
On a 4-wire delta high-leg system, how must the high-leg (stinger) conductor be identified per NEC 110.15?
The phase conductor with the higher voltage to ground (the high leg, $\approx 208\,\text{V}$ to neutral) must be marked orange or by other effective means at any point where the neutral is also present.
What does NEC permit for re-identifying a white conductor used as an ungrounded conductor in a cable assembly?
In cables (e.g., for switch loops), a white conductor may be reidentified as ungrounded by permanently marking it with a color other than white, gray, or green (such as black tape or paint) at each visible/accessible termination.
Compare RMC, IMC, and EMT: which is threaded heavy-wall, which is thinner threaded, and which is thin-wall threadless?
RMC (Rigid Metal Conduit) = thickest, threaded; IMC (Intermediate Metal Conduit) = lighter wall than RMC but still threaded, same outside diameter; EMT (Electrical Metallic Tubing) = thin-wall, not threaded, uses set-screw or compression fittings.
What do the abbreviations PVC, ENT, LFNC, and LFMC stand for in conduit/tubing wiring methods?
PVC = Rigid Polyvinyl Chloride Conduit (Article 352); ENT = Electrical Nonmetallic Tubing (flexible corrugated, Article 362); LFNC = Liquidtight Flexible Nonmetallic Conduit (356); LFMC = Liquidtight Flexible Metal Conduit (350).
Which two PVC conduit wall thicknesses are most common, and how do they differ?
Schedule 40 (thinner wall, normal duty) and Schedule 80 (thicker wall, reduced interior area, used where subject to physical damage). Schedule 80 has lower fill capacity for the same trade size.
Why must EMT and other metal raceways not be used as the sole equipment ground in some cases, and what governs raceway-as-EGC?
NEC 250.118 lists which raceways qualify as equipment grounding conductors. EMT, RMC, and IMC qualify when properly installed with listed fittings; flexible types (FMC/LFMC) qualify only within length and ampere limits, otherwise a separate EGC is required.
Show the other 31 Wiring Methods, Materials, and Equipment flashcards
State the NEC conduit fill limits for 1 conductor, 2 conductors, and 3 or more conductors (Chapter 9, Table 1).
1 conductor $= 53\%$ of conduit area; 2 conductors $= 31\%$; 3 or more conductors $= 40\%$ of the conduit cross-sectional area.
Why is the 2-conductor fill limit ($31\%$) lower than both the 1-conductor ($53\%$) and 3-or-more ($40\%$) limits?
With exactly two conductors, the geometry leaves a narrow elliptical clearance that increases jamming risk during a pull, so the code uses a more conservative $31\%$ to ease pulling.
What is the maximum total bend allowed between pull points in a conduit run, and why?
A maximum of $360^{\circ}$ total bends (e.g., four $90^{\circ}$ bends) between pull boxes/outlets is permitted, to limit pulling tension and conductor damage.
For EMT, what is the typical take-up (deduction) used when bending a $90^{\circ}$ stub for 1/2", 3/4", and 1" conduit?
$\tfrac{1}{2}" = 5"$ take-up, $\tfrac{3}{4}" = 6"$, $1" = 8"$. The bender is placed at (desired stub height $-$ take-up) measured from the conduit end.
Give the multiplier used to calculate the diagonal (travel) length of an offset bend for common angles $22.5^{\circ}$, $30^{\circ}$, and $45^{\circ}$.
Multiplier $= \dfrac{1}{\sin\theta}$: for $22.5^{\circ}\approx 2.6$, for $30^{\circ}=2.0$, for $45^{\circ}\approx 1.4$. Distance between bends $=$ offset depth $\times$ multiplier.
What is the minimum bending radius concern for conductors and what governs it?
Bends must not damage the raceway or reduce its internal diameter; NEC Chapter 9 Table 2 gives minimum bend radii by trade size. For conductors entering boxes/cabinets, 312.6 sets minimum bending space at terminals to prevent conductor damage.
State the free-space volume allowance (in $\text{in}^3$) per conductor for box fill at 14, 12, and 10 AWG (Table 314.16(B)).
14 AWG $= 2.00\,\text{in}^3$, 12 AWG $= 2.25\,\text{in}^3$, 10 AWG $= 2.50\,\text{in}^3$ per conductor.
In box-fill counting, how are equipment grounding conductors and internal cable clamps counted?
All equipment grounding conductors together count as ONE conductor (based on the largest EGC). All internal cable clamps together count as ONE conductor (based on the largest conductor in the box). Each is a single volume allowance.
How is a single yoke/strap (switch or receptacle) counted in box fill?
Each yoke or strap supporting a device counts as TWO conductors, based on the largest conductor connected to that device. (Wide devices spanning multiple gangs count double per the gangs they occupy.)
How are conductors that pass through a box without splice or termination counted in box fill, versus those that originate outside and terminate inside?
A conductor running through the box unbroken counts as ONE. A conductor that enters and terminates (or is spliced) in the box counts as ONE. Conductors that both originate and end within the box (pigtails) are not counted.
Box-fill example: A 4" square box ($21\,\text{in}^3$) contains six 12 AWG conductors, two internal clamps, and one duplex receptacle (12 AWG) plus one 12 AWG EGC. Does it comply?
Count: 6 conductors $+$ 2 for the device yoke $+$ 1 for all clamps $+$ 1 for all grounds $= 10$ units $\times 2.25 = 22.5\,\text{in}^3$. This exceeds $21\,\text{in}^3$, so it does NOT comply; a deeper box is required.
What do the cable abbreviations NM, NMC, AC, MC, and SE designate?
NM = Nonmetallic-sheathed cable (Romex, dry locations, Art. 334); NMC = corrosion-resistant NM; AC = Armored Cable (BX, Art. 320); MC = Metal-Clad cable (Art. 330); SE = Service-Entrance cable (Art. 338).
What is the key grounding difference between AC cable and MC cable?
AC cable's armor (with internal bonding strip) is listed as the equipment grounding path. MC cable's armor is NOT an approved EGC, so MC contains a separate dedicated equipment grounding conductor.
State the support and securing requirements for NM cable per NEC 334.30.
NM cable must be secured within $12"$ of each box/enclosure and supported at least every $4.5\,\text{ft}$ ($54"$) along the run.
When NM cable passes through or is run on framing members, what protection from physical damage is required?
Where run through bored holes, the hole must be $\geq 1\tfrac{1}{4}"$ from the nearest edge; otherwise a $\tfrac{1}{16}"$ steel plate is required. Along the face of studs/rafters it must be protected or kept $\geq 1\tfrac{1}{4}"$ back, per NEC 300.4.
Where is NM cable (Type NM-B) NOT permitted to be used?
NM is prohibited in wet/damp locations, where exposed to corrosive fumes, embedded in concrete/masonry, and (per 334.10/334.12) as service-entrance cable or in certain commercial structures of Types I/II construction.
What is the maximum continuous current rating relationship for a switch (Article 404), and how must general-use snap switches be rated?
Snap switches must be used within their ampere and voltage rating. AC general-use snap switches control AC loads up to their rating and may control inductive loads up to the rated amperes; tungsten (T-rated) switches are required for high-inrush incandescent loads exceeding the AC rating.
Per NEC 404.2(C), what conductor is generally required at switch locations controlling lighting loads?
A grounded (neutral) conductor must be provided at most switch points controlling lighting loads, so electronic/occupancy switches that need standby power can be installed without using the EGC for return current.
How must snap switches be grounded and what is the rule about metal faceplates (404.9)?
Snap switches, including dimmers, must be effectively grounded via the metal yoke connected to an EGC or grounded metal box. Metal faceplates must be grounded; switches in metal faceplate installations require the grounding means to prevent shock.
What is the required mounting position rule for a knife switch and the 'up = on' convention for switches?
For vertically mounted switches/circuit breakers, the up position must be ON (NEC 240.81/404.7). Knife switches must be connected so the blades are de-energized when open.
At what height and condition can a switch serve as the disconnect, and what indicates switch position requirements (404.7)?
General-use switches must clearly indicate ON/OFF. Where used as a disconnecting means and operable from a readily accessible place, the center of the grip must be $\leq 6\,\text{ft }7\,\text{in}$ ($2.0\,\text{m}$) above the floor/working platform.
Per Article 406, when must receptacles be of the tamper-resistant (TR) type?
125 V and 250 V, 15 A and 20 A receptacles in dwelling units (and many other locations like guest rooms, child care, waiting rooms) must be listed tamper-resistant to prevent insertion of foreign objects.
What is the NEC requirement for receptacles installed in wet locations versus damp locations (406.9)?
Damp locations: a weatherproof cover that protects when no plug is inserted (closes when unused). Wet locations: a weatherproof 'in-use' (bubble) cover that protects even with a cord plugged in, for 15/20 A, 125/250 V receptacles.
How must a receptacle be grounded, and what is required when replacing a non-grounding receptacle where no EGC exists (406.4)?
Receptacles must connect to an EGC. Where no EGC exists, replacement options are: a non-grounding type, OR a GFCI-protected receptacle marked 'No Equipment Ground,' OR a grounding type supplied through a GFCI and marked accordingly.
What is the orientation/face-up rule for receptacles installed in countertops or work surfaces (406.5)?
Receptacles must not be installed in a face-up position in countertops or similar work surfaces unless listed for that application, to prevent debris and liquid accumulation in the contacts.
Define a cord connector (cord cap/attachment plug) requirement that the grounding contact must do per Article 406.
Attachment plugs and cord connectors must be made so the grounding pole connection (first to make, last to break) is established before the current-carrying contacts, ensuring grounding continuity precedes energization.
Per Article 410, what clearance must luminaires in clothes closets maintain from the storage space, for surface and recessed fixtures?
Surface-mounted incandescent/LED with completely enclosed light source: $12"$ from storage; surface fluorescent/LED: $6"$; recessed incandescent/LED enclosed: $6"$; recessed fluorescent: $6"$. Open/exposed incandescent lamps are prohibited in closets (410.16).
What is the requirement for luminaires used in wet or damp locations (410.10)?
Luminaires must be listed and marked for the location: 'Suitable for Wet Locations' for wet, 'Suitable for Damp Locations' for damp. Fixtures must be constructed/installed so water cannot accumulate in wiring compartments, lampholders, or other parts.
For recessed luminaires, what distinguishes Type IC from non-IC, and the clearance rule (410.116)?
Type IC luminaires are listed for direct contact with thermal insulation. Non-IC types must have insulation kept $\geq 3"$ away and no combustible material above the fixture except at support points; both limit recessed housing surface temperature for fire safety.
What is the maximum weight a luminaire can be supported by an outlet box alone, and when is independent support required (314.27 / 410.36)?
An outlet box listed for fixture support may support a luminaire up to $50\,\text{lb}$; luminaires heavier than $50\,\text{lb}$ must be supported independently of the outlet box. Boxes supporting ceiling paddle fans must be listed and marked for fan support.
Compare line voltage versus low-voltage lighting per Article 411, and the voltage threshold.
Article 411 covers lighting systems operating at $\leq 30\,\text{V}$ (low-voltage, e.g., $12\,\text{V}$ track/landscape), which must be listed as a complete system or assembled from listed parts. Standard line-voltage luminaires operate at $120/277\,\text{V}$ under Article 410.
Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment FAQ
What is in the Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment syllabus?
Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment is split into 3 chapters: Conductors and Insulation, Raceways, Boxes, and Fittings and Switches, Receptacles, and Luminaires. Together they contain 10 topics and 23 sub-topics.
How many chapters are in Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment?
3 chapters, containing 10 topics and 23 sub-topics. The largest chapter is Raceways, Boxes, and Fittings, with 4 topics.
Are there flashcards for Journeyman/Master Electrician License Exam Wiring Methods, Materials, and Equipment?
Yes — a 51-card Wiring Methods, Materials, and Equipment deck, printed in full in the flashcards section of this page and available in the Examius app with spaced repetition. The free plan covers one exam of your choice, including its flashcards; Examius Pro, a one-time purchase, unlocks every other exam and deck.